[{"data":1,"prerenderedAt":1147},["ShallowReactive",2],{"blog-post-de-steckdosen-pro-stromkreis":3,"blog-alternates-sockets-per-circuit":274},{"id":4,"title":5,"articleId":6,"body":7,"category":246,"date":247,"description":248,"extension":249,"lastUpdated":247,"locale":250,"meta":251,"navigation":252,"path":253,"publishDate":247,"readTime":254,"refreshInterval":255,"seo":256,"slug":257,"stem":258,"tags":259,"__hash__":273},"blog\u002Fblog\u002Fsockets-per-circuit.de.md","Wie viele Steckdosen pro Stromkreis? (AREI-Grenzwerte)","sockets-per-circuit",{"type":8,"value":9,"toc":236},"minimark",[10,15,32,36,93,97,158,162,165,187,200,204,211,215,230],[11,12,14],"h2",{"id":13},"maximal-8-punkte-pro-stromkreis","Maximal 8 Punkte pro Stromkreis",[16,17,18,19,23,24,27,28,31],"p",{},"Das AREI legt in ",[20,21,22],"strong",{},"Art. 5.3.5.2b"," fest: Pro Endstromkreis dürfen maximal ",[20,25,26],{},"8 Einzel- oder Mehrfachsteckdosen"," installiert werden. Dabei gilt eine wichtige Zählregel — eine Doppelsteckdose zählt als ",[20,29,30],{},"ein"," Punkt, nicht als zwei.",[11,33,35],{"id":34},"zählregeln-im-detail","Zählregeln im Detail",[37,38,39,52],"table",{},[40,41,42],"thead",{},[43,44,45,49],"tr",{},[46,47,48],"th",{},"Anschluss",[46,50,51],{},"Zählt als",[53,54,55,64,71,78,85],"tbody",{},[43,56,57,61],{},[58,59,60],"td",{},"Einfachsteckdose",[58,62,63],{},"1 Punkt",[43,65,66,69],{},[58,67,68],{},"Doppelsteckdose",[58,70,63],{},[43,72,73,76],{},[58,74,75],{},"Dreifachsteckdose",[58,77,63],{},[43,79,80,83],{},[58,81,82],{},"Lichtauslass",[58,84,63],{},[43,86,87,90],{},[58,88,89],{},"Festanschluss (Herd, Backofen)",[58,91,92],{},"Eigener Stromkreis",[11,94,96],{"id":95},"kabel-und-sicherung-pro-stromkreis-typ","Kabel und Sicherung pro Stromkreis-Typ",[37,98,99,115],{},[40,100,101],{},[43,102,103,106,109,112],{},[46,104,105],{},"Stromkreis-Typ",[46,107,108],{},"Kabel",[46,110,111],{},"Sicherung",[46,113,114],{},"Max. Punkte",[53,116,117,131,144],{},[43,118,119,122,125,128],{},[58,120,121],{},"Steckdosen",[58,123,124],{},"XVB 3G2,5",[58,126,127],{},"16A oder 20A",[58,129,130],{},"8",[43,132,133,136,139,142],{},[58,134,135],{},"Beleuchtung",[58,137,138],{},"XVB 3G1,5",[58,140,141],{},"10A oder 16A",[58,143,130],{},[43,145,146,149,152,155],{},[58,147,148],{},"Dediziert (Herd)",[58,150,151],{},"XVB 3G4 → 25A, XVB 3G6 → 32A",[58,153,154],{},"25A oder 32A",[58,156,157],{},"1",[11,159,161],{"id":160},"praxisbeispiel-typisches-einfamilienhaus","Praxisbeispiel: Typisches Einfamilienhaus",[16,163,164],{},"Ein Einfamilienhaus mit 3 Schlafzimmern, Küche, Bad und Wohnzimmer braucht typischerweise:",[166,167,168,175,181],"ul",{},[169,170,171,174],"li",{},[20,172,173],{},"5–7 Steckdosen-Stromkreise"," (Wohnräume, Küche, Schlafzimmer)",[169,176,177,180],{},[20,178,179],{},"3–4 Lichtstromkreise"," (Erdgeschoss, Obergeschoss, Außenbeleuchtung)",[169,182,183,186],{},[20,184,185],{},"3–4 dedizierte Stromkreise"," (Backofen, Kochfeld, Spülmaschine, Trockner)",[188,189,190],"blockquote",{},[16,191,192,195,196,199],{},[20,193,194],{},"Achtung",": Küchen brauchen oft eigene dedizierte Stromkreise für Spülmaschine, Backofen und Kochfeld. Diese Geräte werden fest angeschlossen und zählen ",[20,197,198],{},"nicht"," als normale Steckdose — sie erhalten jeweils einen eigenen Stromkreis mit stärkerem Kabel und passender Sicherung.",[11,201,203],{"id":202},"altbau-regelung-arei-part-8","Altbau-Regelung (AREI Part 8)",[16,205,206,207,210],{},"Bei Bestandsanlagen, die vor dem aktuellen AREI errichtet wurden, erlaubt ",[20,208,209],{},"Part 8"," unter bestimmten Bedingungen mehr als 8 Punkte pro Stromkreis — vorausgesetzt, die Gesamtbelastung bleibt vertretbar und der Kabelquerschnitt ist ausreichend dimensioniert. Bei einer Renovierung oder Erweiterung gelten jedoch die aktuellen Grenzwerte.",[11,212,214],{"id":213},"verwandte-artikel","Verwandte Artikel",[166,216,217,224],{},[169,218,219],{},[220,221,223],"a",{"href":222},"\u002Fde\u002Fblog\u002F30ma-fi-pro-steckdose","Brauche ich einen 30mA FI-Schalter für jede Steckdose?",[169,225,226],{},[220,227,229],{"href":228},"\u002Fde\u002Fblog\u002Felektrische-abnahme","Elektrische Abnahme in Belgien — was Sie wissen müssen",[16,231,232],{},[220,233,235],{"href":234},"\u002F","Erstellen Sie jetzt Ihr AREI-konformes Eindrahtschema — kostenlos →",{"title":237,"searchDepth":238,"depth":238,"links":239},"",2,[240,241,242,243,244,245],{"id":13,"depth":238,"text":14},{"id":34,"depth":238,"text":35},{"id":95,"depth":238,"text":96},{"id":160,"depth":238,"text":161},{"id":202,"depth":238,"text":203},{"id":213,"depth":238,"text":214},"faq","2026-03-11","Maximal 8 Punkte pro Stromkreis — aber wie zählt man richtig? Erfahren Sie die AREI-Regeln für Steckdosen, Beleuchtung und dedizierte Stromkreise.","md","de",{},true,"\u002Fblog\u002Fsockets-per-circuit.de","3 min",12,{"title":5,"description":248},"steckdosen-pro-stromkreis","blog\u002Fsockets-per-circuit.de",[260,261,262,263,111,108,264,265,266,267,268,269,270,271,272],"AREI","RGIE","Steckdose","Stromkreis","XVB","Eindrahtschema","Eendraadschema","Stromabnahme","Keuring","elektrische Installation","Belgien","schéma unifilaire","Situationsplan","z2g7vvhEZpHUUqR3P13C2pKL9huebIaeHq-9BMYLZk0",[275,439,679,913],{"id":4,"title":5,"articleId":6,"body":276,"category":246,"date":247,"description":248,"extension":249,"lastUpdated":247,"locale":250,"meta":436,"navigation":252,"path":253,"publishDate":247,"readTime":254,"refreshInterval":255,"seo":437,"slug":257,"stem":258,"tags":438,"__hash__":273},{"type":8,"value":277,"toc":428},[278,280,288,290,332,334,380,382,384,398,406,408,412,414,424],[11,279,14],{"id":13},[16,281,18,282,23,284,27,286,31],{},[20,283,22],{},[20,285,26],{},[20,287,30],{},[11,289,35],{"id":34},[37,291,292,300],{},[40,293,294],{},[43,295,296,298],{},[46,297,48],{},[46,299,51],{},[53,301,302,308,314,320,326],{},[43,303,304,306],{},[58,305,60],{},[58,307,63],{},[43,309,310,312],{},[58,311,68],{},[58,313,63],{},[43,315,316,318],{},[58,317,75],{},[58,319,63],{},[43,321,322,324],{},[58,323,82],{},[58,325,63],{},[43,327,328,330],{},[58,329,89],{},[58,331,92],{},[11,333,96],{"id":95},[37,335,336,348],{},[40,337,338],{},[43,339,340,342,344,346],{},[46,341,105],{},[46,343,108],{},[46,345,111],{},[46,347,114],{},[53,349,350,360,370],{},[43,351,352,354,356,358],{},[58,353,121],{},[58,355,124],{},[58,357,127],{},[58,359,130],{},[43,361,362,364,366,368],{},[58,363,135],{},[58,365,138],{},[58,367,141],{},[58,369,130],{},[43,371,372,374,376,378],{},[58,373,148],{},[58,375,151],{},[58,377,154],{},[58,379,157],{},[11,381,161],{"id":160},[16,383,164],{},[166,385,386,390,394],{},[169,387,388,174],{},[20,389,173],{},[169,391,392,180],{},[20,393,179],{},[169,395,396,186],{},[20,397,185],{},[188,399,400],{},[16,401,402,195,404,199],{},[20,403,194],{},[20,405,198],{},[11,407,203],{"id":202},[16,409,206,410,210],{},[20,411,209],{},[11,413,214],{"id":213},[166,415,416,420],{},[169,417,418],{},[220,419,223],{"href":222},[169,421,422],{},[220,423,229],{"href":228},[16,425,426],{},[220,427,235],{"href":234},{"title":237,"searchDepth":238,"depth":238,"links":429},[430,431,432,433,434,435],{"id":13,"depth":238,"text":14},{"id":34,"depth":238,"text":35},{"id":95,"depth":238,"text":96},{"id":160,"depth":238,"text":161},{"id":202,"depth":238,"text":203},{"id":213,"depth":238,"text":214},{},{"title":5,"description":248},[260,261,262,263,111,108,264,265,266,267,268,269,270,271,272],{"id":440,"title":441,"articleId":6,"body":442,"category":246,"date":247,"description":660,"extension":249,"lastUpdated":247,"locale":661,"meta":662,"navigation":252,"path":663,"publishDate":247,"readTime":254,"refreshInterval":255,"seo":664,"slug":6,"stem":665,"tags":666,"__hash__":678},"blog\u002Fblog\u002Fsockets-per-circuit.en.md","How Many Sockets Per Circuit? (AREI Limits)",{"type":8,"value":443,"toc":652},[444,448,462,466,517,521,580,584,587,607,619,623,629,633,647],[11,445,447],{"id":446},"maximum-8-points-per-circuit","Maximum 8 points per circuit",[16,449,450,451,453,454,457,458,461],{},"The AREI specifies in ",[20,452,22],{},": a maximum of ",[20,455,456],{},"8 single or multiple socket outlets"," may be installed per final circuit. An important counting rule applies — a double socket counts as ",[20,459,460],{},"one"," point, not two.",[11,463,465],{"id":464},"counting-rules-in-detail","Counting rules in detail",[37,467,468,478],{},[40,469,470],{},[43,471,472,475],{},[46,473,474],{},"Connection",[46,476,477],{},"Counts as",[53,479,480,488,495,502,509],{},[43,481,482,485],{},[58,483,484],{},"Single socket",[58,486,487],{},"1 point",[43,489,490,493],{},[58,491,492],{},"Double socket",[58,494,487],{},[43,496,497,500],{},[58,498,499],{},"Triple socket",[58,501,487],{},[43,503,504,507],{},[58,505,506],{},"Light outlet",[58,508,487],{},[43,510,511,514],{},[58,512,513],{},"Fixed connection (oven, hob)",[58,515,516],{},"Dedicated circuit",[11,518,520],{"id":519},"cable-and-breaker-per-circuit-type","Cable and breaker per circuit type",[37,522,523,539],{},[40,524,525],{},[43,526,527,530,533,536],{},[46,528,529],{},"Circuit type",[46,531,532],{},"Cable",[46,534,535],{},"Breaker",[46,537,538],{},"Max. points",[53,540,541,554,567],{},[43,542,543,546,549,552],{},[58,544,545],{},"Sockets",[58,547,548],{},"XVB 3G2.5",[58,550,551],{},"16A or 20A",[58,553,130],{},[43,555,556,559,562,565],{},[58,557,558],{},"Lighting",[58,560,561],{},"XVB 3G1.5",[58,563,564],{},"10A or 16A",[58,566,130],{},[43,568,569,572,575,578],{},[58,570,571],{},"Dedicated (oven)",[58,573,574],{},"XVB 3G4 or 3G6",[58,576,577],{},"20A or 32A",[58,579,157],{},[11,581,583],{"id":582},"practical-example-typical-single-family-home","Practical example: typical single-family home",[16,585,586],{},"A single-family home with 3 bedrooms, kitchen, bathroom, and living room typically requires:",[166,588,589,595,601],{},[169,590,591,594],{},[20,592,593],{},"5–7 socket circuits"," (living areas, kitchen, bedrooms)",[169,596,597,600],{},[20,598,599],{},"3–4 lighting circuits"," (ground floor, upper floor, outdoor lighting)",[169,602,603,606],{},[20,604,605],{},"3–4 dedicated circuits"," (oven, hob, dishwasher, dryer)",[188,608,609],{},[16,610,611,614,615,618],{},[20,612,613],{},"Warning",": Kitchens often need dedicated circuits for the dishwasher, oven, and hob. These appliances are hardwired and do ",[20,616,617],{},"not"," count as regular sockets — each gets its own circuit with heavier cable and an appropriately rated breaker.",[11,620,622],{"id":621},"existing-installations-arei-part-8","Existing installations (AREI Part 8)",[16,624,625,626,628],{},"For existing installations built before the current AREI, ",[20,627,209],{}," allows more than 8 points per circuit under certain conditions — provided the total load remains reasonable and the cable cross-section is adequately sized. However, when renovating or extending, the current limits apply.",[11,630,632],{"id":631},"related-articles","Related articles",[166,634,635,641],{},[169,636,637],{},[220,638,640],{"href":639},"\u002Fen\u002Fblog\u002F30ma-rcd-per-socket","Do I need a 30mA RCD for every socket?",[169,642,643],{},[220,644,646],{"href":645},"\u002Fen\u002Fblog\u002Felectrical-inspection","Electrical inspection in Belgium — what you need to know",[16,648,649],{},[220,650,651],{"href":234},"Create your AREI-compliant single-line diagram now — free →",{"title":237,"searchDepth":238,"depth":238,"links":653},[654,655,656,657,658,659],{"id":446,"depth":238,"text":447},{"id":464,"depth":238,"text":465},{"id":519,"depth":238,"text":520},{"id":582,"depth":238,"text":583},{"id":621,"depth":238,"text":622},{"id":631,"depth":238,"text":632},"Maximum 8 points per circuit — but how do you count correctly? Learn the AREI rules for sockets, lighting, and dedicated circuits.","en",{},"\u002Fblog\u002Fsockets-per-circuit.en",{"title":441,"description":660},"blog\u002Fsockets-per-circuit.en",[260,261,667,668,669,670,264,671,672,265,271,673,674,675,676,677],"socket","circuit","breaker","cable","single-line diagram","eendraadschema","inspection","keuring","electrical installation","Belgium","situation plan","mwp_PStl1s1BARAI_qBJqAJMDLGOsZKXOSTAEvhXUOg",{"id":680,"title":681,"articleId":6,"body":682,"category":246,"date":247,"description":897,"extension":249,"lastUpdated":247,"locale":898,"meta":899,"navigation":252,"path":900,"publishDate":247,"readTime":254,"refreshInterval":255,"seo":901,"slug":902,"stem":903,"tags":904,"__hash__":912},"blog\u002Fblog\u002Fsockets-per-circuit.fr.md","Combien de prises par circuit ? (Limites RGIE)",{"type":8,"value":683,"toc":889},[684,688,702,706,756,760,816,820,823,843,855,859,866,870,884],[11,685,687],{"id":686},"maximum-8-points-par-circuit","Maximum 8 points par circuit",[16,689,690,691,693,694,697,698,701],{},"Le RGIE stipule à l'",[20,692,22],{}," : un maximum de ",[20,695,696],{},"8 prises simples ou multiples"," peut être installé par circuit terminal. Une règle de comptage importante s'applique — une prise double compte comme ",[20,699,700],{},"un"," seul point, pas deux.",[11,703,705],{"id":704},"règles-de-comptage-en-détail","Règles de comptage en détail",[37,707,708,718],{},[40,709,710],{},[43,711,712,715],{},[46,713,714],{},"Raccordement",[46,716,717],{},"Compte comme",[53,719,720,727,734,741,748],{},[43,721,722,725],{},[58,723,724],{},"Prise simple",[58,726,487],{},[43,728,729,732],{},[58,730,731],{},"Prise double",[58,733,487],{},[43,735,736,739],{},[58,737,738],{},"Prise triple",[58,740,487],{},[43,742,743,746],{},[58,744,745],{},"Point lumineux",[58,747,487],{},[43,749,750,753],{},[58,751,752],{},"Raccordement fixe (four, taque)",[58,754,755],{},"Circuit dédié",[11,757,759],{"id":758},"câble-et-disjoncteur-par-type-de-circuit","Câble et disjoncteur par type de circuit",[37,761,762,777],{},[40,763,764],{},[43,765,766,769,772,775],{},[46,767,768],{},"Type de circuit",[46,770,771],{},"Câble",[46,773,774],{},"Disjoncteur",[46,776,538],{},[53,778,779,791,803],{},[43,780,781,784,786,789],{},[58,782,783],{},"Prises",[58,785,124],{},[58,787,788],{},"16A ou 20A",[58,790,130],{},[43,792,793,796,798,801],{},[58,794,795],{},"Éclairage",[58,797,138],{},[58,799,800],{},"10A ou 16A",[58,802,130],{},[43,804,805,808,811,814],{},[58,806,807],{},"Dédié (four)",[58,809,810],{},"XVB 3G4 ou 3G6",[58,812,813],{},"20A ou 32A",[58,815,157],{},[11,817,819],{"id":818},"exemple-pratique-maison-unifamiliale-typique","Exemple pratique : maison unifamiliale typique",[16,821,822],{},"Une maison unifamiliale avec 3 chambres, cuisine, salle de bain et salon nécessite généralement :",[166,824,825,831,837],{},[169,826,827,830],{},[20,828,829],{},"5 à 7 circuits prises"," (pièces de vie, cuisine, chambres)",[169,832,833,836],{},[20,834,835],{},"3 à 4 circuits éclairage"," (rez-de-chaussée, étage, éclairage extérieur)",[169,838,839,842],{},[20,840,841],{},"3 à 4 circuits dédiés"," (four, taque de cuisson, lave-vaisselle, sèche-linge)",[188,844,845],{},[16,846,847,850,851,854],{},[20,848,849],{},"Attention"," : Les cuisines nécessitent souvent des circuits dédiés pour le lave-vaisselle, le four et la taque de cuisson. Ces appareils sont raccordés en fixe et ne comptent ",[20,852,853],{},"pas"," comme des prises normales — chacun dispose de son propre circuit avec un câble plus fort et un disjoncteur adapté.",[11,856,858],{"id":857},"installations-existantes-rgie-partie-8","Installations existantes (RGIE Partie 8)",[16,860,861,862,865],{},"Pour les installations existantes construites avant le RGIE actuel, la ",[20,863,864],{},"Partie 8"," autorise plus de 8 points par circuit sous certaines conditions — à condition que la charge totale reste raisonnable et que la section du câble soit suffisamment dimensionnée. Toutefois, en cas de rénovation ou d'extension, les limites actuelles s'appliquent.",[11,867,869],{"id":868},"articles-connexes","Articles connexes",[166,871,872,878],{},[169,873,874],{},[220,875,877],{"href":876},"\u002Ffr\u002Fblog\u002F30ma-ddr-par-prise","Ai-je besoin d'un différentiel 30mA par prise ?",[169,879,880],{},[220,881,883],{"href":882},"\u002Ffr\u002Fblog\u002Fcontrole-electrique","Contrôle électrique en Belgique — ce qu'il faut savoir",[16,885,886],{},[220,887,888],{"href":234},"Créez votre schéma unifilaire conforme RGIE — gratuit →",{"title":237,"searchDepth":238,"depth":238,"links":890},[891,892,893,894,895,896],{"id":686,"depth":238,"text":687},{"id":704,"depth":238,"text":705},{"id":758,"depth":238,"text":759},{"id":818,"depth":238,"text":819},{"id":857,"depth":238,"text":858},{"id":868,"depth":238,"text":869},"Maximum 8 points par circuit — mais comment compter correctement ? Découvrez les règles du RGIE pour les prises, l'éclairage et les circuits dédiés.","fr",{},"\u002Fblog\u002Fsockets-per-circuit.fr",{"title":681,"description":897},"prises-par-circuit","blog\u002Fsockets-per-circuit.fr",[260,261,905,668,906,907,264,271,672,908,909,910,265,911],"prise","disjoncteur","câble","contrôle électrique","installation électrique","Belgique","plan de situation","IU-kGbBFs_8xwa1wbV4WIEStsLBZEjX__-wAl3TL-uQ",{"id":914,"title":915,"articleId":6,"body":916,"category":246,"date":247,"description":1131,"extension":249,"lastUpdated":247,"locale":1132,"meta":1133,"navigation":252,"path":1134,"publishDate":247,"readTime":254,"refreshInterval":255,"seo":1135,"slug":1136,"stem":1137,"tags":1138,"__hash__":1146},"blog\u002Fblog\u002Fsockets-per-circuit.nl.md","Hoeveel stopcontacten per stroomkring? (AREI-limieten)",{"type":8,"value":917,"toc":1123},[918,922,936,940,991,995,1050,1054,1057,1077,1089,1093,1100,1104,1118],[11,919,921],{"id":920},"maximaal-8-punten-per-stroomkring","Maximaal 8 punten per stroomkring",[16,923,924,925,927,928,931,932,935],{},"Het AREI bepaalt in ",[20,926,22],{},": per eindkring mogen maximaal ",[20,929,930],{},"8 enkel- of meervoudige stopcontacten"," worden geïnstalleerd. Daarbij geldt een belangrijke telregel — een dubbel stopcontact telt als ",[20,933,934],{},"één"," punt, niet als twee.",[11,937,939],{"id":938},"telregels-in-detail","Telregels in detail",[37,941,942,952],{},[40,943,944],{},[43,945,946,949],{},[46,947,948],{},"Aansluiting",[46,950,951],{},"Telt als",[53,953,954,962,969,976,983],{},[43,955,956,959],{},[58,957,958],{},"Enkelvoudig stopcontact",[58,960,961],{},"1 punt",[43,963,964,967],{},[58,965,966],{},"Dubbel stopcontact",[58,968,961],{},[43,970,971,974],{},[58,972,973],{},"Drievoudig stopcontact",[58,975,961],{},[43,977,978,981],{},[58,979,980],{},"Lichtpunt",[58,982,961],{},[43,984,985,988],{},[58,986,987],{},"Vaste aansluiting (oven, kookplaat)",[58,989,990],{},"Eigen kring",[11,992,994],{"id":993},"kabel-en-automaat-per-type-stroomkring","Kabel en automaat per type stroomkring",[37,996,997,1012],{},[40,998,999],{},[43,1000,1001,1004,1006,1009],{},[46,1002,1003],{},"Type stroomkring",[46,1005,108],{},[46,1007,1008],{},"Automaat",[46,1010,1011],{},"Max. punten",[53,1013,1014,1026,1038],{},[43,1015,1016,1019,1021,1024],{},[58,1017,1018],{},"Stopcontacten",[58,1020,124],{},[58,1022,1023],{},"16A of 20A",[58,1025,130],{},[43,1027,1028,1031,1033,1036],{},[58,1029,1030],{},"Verlichting",[58,1032,138],{},[58,1034,1035],{},"10A of 16A",[58,1037,130],{},[43,1039,1040,1042,1045,1048],{},[58,1041,571],{},[58,1043,1044],{},"XVB 3G4 of 3G6",[58,1046,1047],{},"20A of 32A",[58,1049,157],{},[11,1051,1053],{"id":1052},"praktijkvoorbeeld-typische-eengezinswoning","Praktijkvoorbeeld: typische eengezinswoning",[16,1055,1056],{},"Een eengezinswoning met 3 slaapkamers, keuken, badkamer en woonkamer heeft doorgaans nodig:",[166,1058,1059,1065,1071],{},[169,1060,1061,1064],{},[20,1062,1063],{},"5–7 stopcontactkringen"," (leefruimtes, keuken, slaapkamers)",[169,1066,1067,1070],{},[20,1068,1069],{},"3–4 verlichtingskringen"," (gelijkvloers, verdieping, buitenverlichting)",[169,1072,1073,1076],{},[20,1074,1075],{},"3–4 dedicated kringen"," (oven, kookplaat, vaatwasser, droogkast)",[188,1078,1079],{},[16,1080,1081,1084,1085,1088],{},[20,1082,1083],{},"Let op",": Keukens hebben vaak eigen dedicated stroomkringen nodig voor de vaatwasser, oven en kookplaat. Deze toestellen worden vast aangesloten en tellen ",[20,1086,1087],{},"niet"," als gewone stopcontacten — elk krijgt een eigen kring met een zwaardere kabel en een passende automaat.",[11,1090,1092],{"id":1091},"bestaande-installaties-arei-deel-8","Bestaande installaties (AREI Deel 8)",[16,1094,1095,1096,1099],{},"Bij bestaande installaties die vóór het huidige AREI zijn aangelegd, staat ",[20,1097,1098],{},"Deel 8"," onder bepaalde voorwaarden meer dan 8 punten per stroomkring toe — op voorwaarde dat de totale belasting redelijk blijft en de kabeldoorsnede voldoende gedimensioneerd is. Bij renovatie of uitbreiding gelden echter de huidige limieten.",[11,1101,1103],{"id":1102},"gerelateerde-artikelen","Gerelateerde artikelen",[166,1105,1106,1112],{},[169,1107,1108],{},[220,1109,1111],{"href":1110},"\u002Fblog\u002F30ma-aardlek-per-stopcontact","Heb ik een 30mA differentieel nodig per stopcontact?",[169,1113,1114],{},[220,1115,1117],{"href":1116},"\u002Fblog\u002Felektrische-keuring","Elektrische keuring in België — wat u moet weten",[16,1119,1120],{},[220,1121,1122],{"href":234},"Maak nu uw AREI-conform eendraadschema — gratis →",{"title":237,"searchDepth":238,"depth":238,"links":1124},[1125,1126,1127,1128,1129,1130],{"id":920,"depth":238,"text":921},{"id":938,"depth":238,"text":939},{"id":993,"depth":238,"text":994},{"id":1052,"depth":238,"text":1053},{"id":1091,"depth":238,"text":1092},{"id":1102,"depth":238,"text":1103},"Maximaal 8 punten per stroomkring — maar hoe tel je correct? Ontdek de AREI-regels voor stopcontacten, verlichting en dedicated kringen.","nl",{},"\u002Fblog\u002Fsockets-per-circuit.nl",{"title":915,"description":1131},"stopcontacten-per-circuit","blog\u002Fsockets-per-circuit.nl",[260,261,1139,1140,1141,1142,264,672,674,1143,1144,265,271,1145],"stopcontact","stroomkring","automaat","kabel","elektrische installatie","België","situatieschema","BuWg7G13rYSMPY3BvaGO6593YnVaDNke8eA_EF8Yhw0",1775151657946]