FAQ

Which Cables Can I Use in the Bathroom? (AREI Zones)

XVB is always permitted, VOB in conduit only with restrictions. Learn which cable types are allowed in each AREI zone and what to watch out for.

Published on 9 March 2026 4 min min read

XVB is always allowed — VOB only with restrictions

Bathroom electrical installations in Belgium are subject to special regulations. The key rule of thumb: XVB cable (sheathed cable) is permitted in all bathroom zones. VOB wire in conduit (Preflex) has restrictions — especially in hollow walls.

The AREI bathroom zones

The AREI defines three zones around bathtubs and showers: Zone 0, Zone 1, Zone 2 (bathtubs only), and the area outside the zones (Art. 7.1.3.2).

ZoneAreaPermitted installation
Zone 0Inside the bathtub/showerSELV ≤ 12V only, IPX7
Zone 1Vertically above Zone 0, up to 2.25 m heightFixed appliances ≥ IPX4; SELV sockets and SELV switches permitted (Art. 7.1.5.2c Nr. 2 and 4)
Zone 260 cm around Zone 1 — bathtubs onlySockets with 30mA RCD allowed, appliances ≥ IPX4

Important: Zone 2 is not defined for showers (Art. 7.1.3.2 Nr. 3b). For showers, Zone 1 is followed directly by the area outside the zones.

Outside these zones, normal installation rules apply.

Cable types and their permissibility

Cable typeCPR classZone 0Zone 1Zone 2Outside zones
XVB 3G2.5CcaNoYesYesYes
XVB 3G1.5CcaNoYes (lighting)YesYes
VOB in grey PreflexNoYesYesYes
VOB in green PreflexNoNo (hollow wall)RestrictedYes
H07Z1-U (halogen-free)CcaNoYesYesYes

Important notes on cable types

  • XVB (sheathed cable): Always the safe choice. Suitable for flush mounting, surface mounting, and cable trays.
  • Grey Preflex (standard conduit with pre-pulled VOB): Permitted in solid walls. Not allowed in hollow walls or suspended ceilings.
  • Preflex Safe (green): In solid walls, Preflex Safe (Cca) is also permitted in Zone 1. The restriction applies to hollow walls (droogbouw), not the zone itself.
  • H07Z1-U: Halogen-free wire, particularly recommended for sensitive areas. Note: H07Z1-U as a single wire does not inherently have a CPR class of Cca — the class refers to the cable system (wire + conduit). H07Z1-U in Preflex Safe achieves Cca.

Cross-section table

UsageMin. cross-sectionCircuit breaker
Lighting1.5 mm²10A or 16A
Sockets2.5 mm²16A or 20A
Washing machine / dryer2.5 mm²16A (dedicated circuit)
Electric water heater (under-sink, ≤ 2 kW)2.5 mm²16A
Electric instantaneous water heater (18–27 kW)6 mm² (32A) or 10 mm² (40A, three-phase)32A or 40A

30mA differential protection is mandatory

According to AREI Art. 7.1.4.3, all circuits in the bathroom must be protected by a 30mA RCD — no exceptions. This applies equally to lighting, sockets, and fixed appliances.

Warning: Even circuits that merely pass through the bathroom (e.g., cables to the attic) must comply with zone requirements if they run within the protection zones.

Equipotential bonding in the bathroom

Important: The AREI (Art. 7.1.4.4) requires supplementary equipotential bonding in the bathroom — all metallic parts (water pipes, radiators, bathtub, drain pipes) must be connected to each other and to the main earthing terminal via a protective conductor. Missing equipotential bonding is a common reason for inspection failure.

Plan your bathroom electrics with PlanElec — free →