FAQ

Cable Cross-Section per Circuit Breaker: Which Cable for Which Protection?

Which cable cross-section for a 16, 20 or 32 A breaker in Belgium? AREI/RGIE Table 4.11, minimum sizes for socket circuits and what else you need to check.

Published on 18 March 2026 Updated on 5 October 2026 7 min

In Belgian domestic installations, AREI Table 4.11 sets the largest breaker per copper cross-section: 16 A on 1.5 mm², 20 A on 2.5 mm², 25 A on 4 mm² and 40 A on 6 mm². Socket-outlet circuits always use at least 2.5 mm² under subsection 5.2.1.2. The protective device protects the cable, not the appliance: a breaker that is too large for the cross-section trips too late on overload, and the cable overheats.

Quick reference: breaker → minimum cross-section

This overview reads Table 4.11 the way the question comes up on site: the breaker is given, and you need the smallest permitted copper cross-section.

Circuit breakerMinimum copper cross-sectionTypical use
10 A1.5 mm² (Table 4.11 lists 1 mm², but Table 5.1 does not allow 1 mm² for new fixed wiring)Lighting
16 A1.5 mm²; socket-outlet circuits at least 2.5 mm² under 5.2.1.2Lighting, circuits without sockets
20 A2.5 mm²Socket circuit, appliance circuit
25 A4 mm²Final circuit with a higher load
32 A6 mm²Hob, instantaneous water heater
40 A6 mm² (table ceiling)Final circuit or supply cable
63 A10 mm²Supply to a sub-distribution board
80 A16 mm²Supply cable, main switch
100 A25 mm²Supply cable, main switch

The table is a ceiling for the protective device, not a finished cable calculation. Installation method, grouping, ambient temperature and voltage drop can require a larger cross-section; how to check them follows below.

The complete Table 4.11

The AREI states the relationship the other way round: for each conductor cross-section, the largest permitted rating of the protective device, separately for fuses and circuit breakers (subsection 4.4.1.4, applicable to domestic installations).

Table 4.11 — Protective device rating by conductor cross-section (AREI 4.4.1.4)

Conductor cross-sectionMax. fuseMax. circuit breakerUse in domestic installations
0.5 mm²2 A4 Acontrol, monitoring, signalling and measuring circuits only
0.75 mm²4 A6 Acircuits integrated in distribution boards only
1 mm²6 A10 Aexisting wiring from before 17 May 1986 only (Part 8)
1.5 mm²10 A16 Acircuits without socket outlets
2.5 mm²16 A20 Agenerally permitted
4 mm²20 A25 Agenerally permitted
6 mm²32 A40 Agenerally permitted
10 mm²50 A63 Agenerally permitted
16 mm²63 A80 Agenerally permitted
25 mm²80 A100 Agenerally permitted
35 mm²100 A125 Agenerally permitted

The two columns are not interchangeable. For the same cable, the fuse limit sits one step below the breaker limit. Replacing a 16 A fuse with a 20 A breaker on 2.5 mm² raises the rated current, so the circuit needs a fresh assessment.

Table 5.1: the exceptions below 2.5 mm²

Subsection 5.2.1.2 prohibits insulated conductors smaller than 2.5 mm² unless they are an integral part of a machine or appliance. Table 5.1 lists the exceptions exhaustively:

MinimumOnly for
1.5 mm²circuits without socket outlets; only a single socket of up to 2.5 A built into a luminaire is allowed
0.75 mm²circuits integrated in switchgear and controlgear assemblies that supply a single socket outlet
0.5 mm²control, monitoring, signalling and measuring circuits

The 1 mm² row in Table 4.11 therefore does not permit new 1 mm² wiring. Table 4.11 sets how large the protective device may be; Table 5.1 decides whether that cross-section may be installed at all.

Existing installations: 1 mm² wiring

For existing parts of domestic installations, section 8.2.2 (point 5, choice of wiring systems) contains a narrowly defined derogation: EMCB and EMCVB wiring of 1 mm² and CTLB and VTLB wiring of 0.75 mm² may remain in service if on-site execution began before 17 May 1986 and the wiring belongs to circuits without socket outlets. Their protective devices must suit the cross-section. This protects existing wiring; it is not a rule for new work. The age of the installation and the actual cable type must be demonstrable at inspection.

What the table does not decide

A complete selection links three currents: the design current of the load I_B, the rated current of the protective device I_n and the current-carrying capacity of the cable I_Z. As a rule, I_B ≤ I_n ≤ I_Z. I_Z is not a fixed value per mm²: subsection 4.4.1.4 makes it depend on cross-section, insulation, cable construction, installation method and ambient temperature.

So also check:

  • Cable: material, insulation and construction; the table values apply to copper.
  • Installation method: in conduit, in thermal insulation, on the wall, bundled or on a cable tray.
  • Grouping: the number of simultaneously loaded conductors and neighbouring circuits.
  • Environment: ambient temperature and heat dissipation.
  • Length and load: voltage drop over the actual cable length.
  • Short circuit: disconnection conditions, fault-loop impedance and the breaker's breaking capacity against the prospective short-circuit current.

A long run may need a larger cross-section because of voltage drop, and an unfavourable installation method lowers the current-carrying capacity. For non-domestic installations, Table 4.11 is not a blanket ceiling; there you determine I_Z according to the rules of good practice.

Voltage drop: 3% and 5% are guide values, not an AREI limit

Section 5.2.5 ("Voltage drop") requires voltage drop to be limited to the values described in the rules of good practice. Subsection 5.2.1.2 b adds that it must be compatible with safe operation of the connected equipment. The AREI sets no percentage. In practice, designers work with 3% for lighting and 5% for other final circuits: proven guide values for a first check. For long runs, motors, EV charging points or sensitive equipment, calculate with the actual conditions.

The calculation needs cable length, conductor material, cross-section, current, power factor and the supply (single- or three-phase). The guide Voltage drop and cable sizing shows how they interact. For a quick answer, use the free cable sizing calculator.

Replacing an old fuse with a circuit breaker

A classic inspection finding is a protective device that is too large for the installed cross-section. Typical case: in an older installation, fuses were later replaced by breakers and nobody checked the cable behind them.

How to approach it:

  1. Identify the cable: which cross-section and cable type are actually installed, and how?
  2. Classify the existing wiring: does a Part 8 derogation apply, for example to 1 mm² wiring from before 17 May 1986?
  3. Pick the column: for 1.5 mm², Table 4.11 allows at most a 10 A fuse or a 16 A breaker; for 2.5 mm², at most 16 A or 20 A.
  4. Check the circuit type: a socket-outlet circuit needs at least 2.5 mm², regardless of the breaker.

A 20 A breaker on 1.5 mm² is never permitted. The table ceiling is not an invitation to raise the protection either.

AREI basis at a glance

AREI referenceRule
Subsection 4.4.1.4Current-carrying capacity I_Z; Table 4.11 with the maximum fuse and breaker rating per cross-section
Subsection 5.2.1.2Choice of wiring: I_Z ≥ I_B, compatible voltage drop, in principle at least 2.5 mm²
Table 5.1Exhaustive exceptions below 2.5 mm²: 1.5 mm², 0.75 mm² and 0.5 mm² for defined uses
Section 5.2.5Voltage drop limited to the values described in the rules of good practice
Section 8.2.2, point 5Existing before 17 May 1986: EMCB/EMCVB 1 mm² and CTLB/VTLB 0.75 mm² in circuits without sockets

Checking cross-section and protection in PlanElec

In PlanElec, you record the protective device, cross-section and length for every circuit directly in the single-line diagram. The self-check verifies that the cross-section matches the rated current of the protection and calculates voltage drop from the cable length against the 3% and 5% guide values. The exact rule coverage is listed in What the self-check verifies. Installation method, grouping and on-site measurements are assessed by the electrician; the official inspection is carried out by the accredited inspection body.

Further reading

Regulatory basis: AREI/RGIE Book 1, version 06, applicable since 1 April 2026, in particular 4.4.1.4, 5.2.1.2, 5.2.5 and 8.2.2. Official text: FPS Economy.

Check your cable choice right away

Run load, length, supply network and protection through the cable calculator, then carry the circuit into your PlanElec project.

Fictitious sample dossier, available without sign-up.