Guide

Distribution Board Planning: Layout and Sizing According to AREI/RGIE

Plan a distribution board under the AREI/RGIE: main switch, 300 mA and 30 mA RCDs, at most 8 circuits per 30 mA RCD, row allocation, spare capacity and a complete example for a single-family home.

Published on 7 April 2026 Updated on 5 October 2026 13 min

You plan a distribution board (consumer unit, fuse box) in four steps: count the circuits, set the protection chain, distribute the groups across rows and plan spare capacity. The AREI/RGIE, Belgium's general regulations for electrical installations, provides fixed anchor points: a main switch of at least 40 A, an RCD of at most 300 mA at the origin of the installation, then 30 mA RCDs for sockets, lighting, bathroom and laundry appliances – with no more than eight final circuits per device. This guide covers the structure, the rules and a complete example for a single-family home.

Fundamentals: structure of a distribution board

DIN rail

All modules in the board clip onto standardised DIN rails (35 mm top-hat rail to EN 60715). Each rail forms a row.

Module units (TE)

Module width is measured in TE (module units). One TE is 18 mm. Typical widths:

ModuleWidth (TE)
Circuit breaker 1P+N1 TE (compact) or 2 TE
Circuit breaker 2-pole2 TE
Circuit breaker 3-pole3 TE
RCD 2-pole (30/300 mA)2 TE
RCD 4-pole4 TE
Main switch 2-pole2 TE
Main switch 4-pole4 TE
Surge protective device (SPD)2–4 TE
Bell transformer2 TE
Time switch2 TE

The data sheets of the devices you actually install are what counts.

Board sizes

Boards are sized by number of rows and TE per row:

DesignationRowsTE per rowTotal TE
1-row112–1812–18
2-row212–1824–36
3-row312–1836–54
4-row412–1848–72

For the single-family home in the example below, a 4-row board with 18 TE per row (72 TE) fits and leaves plenty of room for later extensions.

What the AREI requires of the enclosure

In domestic installations the board is class I or II, with a back panel that cannot be removed for its entire service life, and a door. It is made of non-combustible, non-hygroscopic material and is easily accessible without special tools (subsection 5.3.5.1, points a and c). Protective devices for circuits on different energy tariffs sit on separate plates at least 10 cm apart or in a separate board, unless the grid operator allows otherwise.

Step 1: count the circuits

List every circuit you need. The example home (3 bedrooms, 150 m², no PV) gives this list:

CircuitNumber in exampleCircuit breaker
Lighting3B10A or B16A (1.5 mm²)
General sockets6B16A or B20A (2.5 mm²)
Oven1B20A with 2.5 mm², B25A with 4 mm²
Hob1B32A with 6 mm² or three-phase per manufacturer
Dishwasher1B16A
Washing machine1B16A
Tumble dryer1B16A
Fridge1B16A
Water heater1B16A or B20A
EV charger (if present)1per manufacturer, e.g. B32A with 6 mm² at 7.4 kW single-phase

The maximum ratings per cross-section are in table 4.11 (subsection 4.4.1.4). Washing machine, tumble dryer, dishwasher, cooker, hob, oven and any appliance with a fixed location rated 2600 W or more get their own circuit (5.2.1.2). A socket circuit feeds at most 8 sockets (5.3.5.2 b); pure lighting circuits have no fixed point limit. More in how many sockets per circuit?.

Step 2: set the protection chain

You arrange protective devices hierarchically, from the supply downwards:

Protection hierarchy

Main switch (min. 40 A)
   └── RCD at the origin ≤ 300 mA (min. Type A, min. 40 A)
        ├── RCD 30 mA #1 (Type A)
        │    ├── MCB Lighting ground floor (B10A)
        │    ├── MCB Lighting first floor (B10A)
        │    ├── MCB Sockets living room (B16A)
        │    └── MCB Sockets hallway (B16A)
        ├── RCD 30 mA #2 (Type A)
        │    ├── MCB Sockets kitchen (B16A)
        │    ├── MCB Oven (B20A)
        │    ├── MCB Dishwasher (B16A)
        │    └── MCB Sockets bedrooms (B16A)
        └── RCD 30 mA #3 (Type A)
             ├── MCB Washing machine (B16A)
             ├── MCB Bathroom (B16A)
             ├── MCB Outdoor (B16A)
             └── MCB Garage (B16A)

With a three-phase connection (3N~400/230 V) you need a 4-pole main switch and RCD, plus multi-pole circuit breakers for three-phase outgoing circuits. The differences between Belgian network types are explained in single-phase or three-phase?.

What the AREI prescribes for the protection chain

ElementRequirementReference
Main switchbreaks all line conductors and, where applicable, the neutral at once; at least 40 A5.3.5.1 b
RCD at the originrated residual operating current at most 300 mA; provides the isolating function4.2.4.3 b
All RCDsat least Type A; at the origin a rated current of at least 40 A; disconnect all active conductors including N5.3.5.3 a and c
30 mA RCDdirectly after the origin; protects at least sockets, lighting, bathroom and washing machine, tumble dryer and dishwasher; at most eight final circuits4.2.4.3 b
Fixed appliancesrefrigeration, cooker, heating and other circuits not listed may sit directly behind the RCD at the origin4.2.4.3 b
Electric wall heating > 25 V ACits own RCD of at most 100 mA4.2.4.3 b

Since version 07 of Book 1 (Royal Decree of 13 August 2026), the inspection body no longer seals the RCD at the origin from 1 November 2026; the 300 mA requirement itself stays. Details are in RCD sealing abolished.

If the earth electrode resistance exceeds 30 Ω

If the dispersion resistance of the earth electrode exceeds 30 Ω, you plan at least two RCDs of high or very high sensitivity. Each covers at most sixteen single or multiple sockets. The remaining circuits at the origin get at least one additional RCD of at most 100 mA per circuit or group of circuits (4.2.4.3 b). Reserve space for these extra devices in the first draft if the earth measurement is still pending.

RCD types

TypeCharacteristicDesign boundary
up to 300 mA, min. Type AProtection at the origin of the dwellingRating and poles must fit; Type S is only one option where time selectivity is demonstrated
up to 30 mA, Type AHigh- or very-high-sensitivity protectionFor the circuits listed in 4.2.4.3 b; check additional equipment conditions in the manufacturer data
Type BAlso detects smooth DC residual currentsOnly where the fault-current spectrum and equipment concept require it; not automatic for every charger or inverter
Type FDetects specified mixed-frequency currentsUse only where the load, product standard and manufacturer documentation call for this characteristic

Equipment with semiconductors can produce disturbing DC components. Subsection 5.3.5.3, point f, lists several permitted solutions, including an RCD that keeps working with such faults or a DC fault-current detector installed in coordination with the RCD.

Selectivity

You demonstrate selectivity between upstream and downstream RCDs from sensitivity, time-current characteristics, manufacturer coordination data and the complete protection concept. A time-delayed device can be part of the solution; on its own it does not guarantee selectivity.

Step 3: distribute the groups across rows

AREI rule: at most 8 final circuits per 30 mA RCD

Under subsection 4.2.4.3 b you connect at most eight final circuits to an RCD of high or very high sensitivity. Four to six circuits per device leaves headroom for later extensions.

Typical row allocation

RowContents
Row 1Main switch, RCD at the origin (300 mA), SPD, possibly bell transformer
Row 2RCD #1 (30 mA) with its circuits (lighting and living-area sockets)
Row 3RCD #2 (30 mA) with its circuits (kitchen and bedrooms)
Row 4RCD #3 (30 mA) with its circuits (bathroom, outdoor, garage, utility)

Step 4: plan spare capacity

Plan free positions; 20 to 30% of the TE is proven practice, not an AREI requirement. With 20 circuit breakers that means at least four to six free TE. Close empty positions with blanking plates.

You need spare capacity for:

  • future loads such as an EV charger, air conditioning or a sauna,
  • redistribution when an RCD carries too many circuits,
  • avoiding a later board replacement.

Spare capacity is more than free TE: also plan free terminals, enough trunking, accessible N and PE bars, room for measurements and a documented direction of extension.

Example: 4-row board for a single-family home

A complete example for a Belgian single-family home (3 bedrooms, 150 m², single-phase, no PV):

Row 1 — Supply and protection (18 TE)

PositionModuleTEFunction
1–2Main switch 2P240 A
3–4RCD 2P2300 mA, Type A, 40 A
5–8SPD4Surge protection
9–10Bell transformer28 V bell
11–18Spare8Blanking plates

Row 2 — Group 1: lighting and living area (18 TE)

PositionModuleTEFunction
1–2RCD 30 mA2Type A
3MCB B10A1Lighting ground floor
4MCB B10A1Lighting first floor
5MCB B10A1Lighting cellar/outdoor
6MCB B16A1Sockets living room
7MCB B16A1Sockets dining room
8MCB B16A1Sockets hallway
9–18Spare10Blanking plates

Row 3 — Group 2: kitchen and bedrooms (18 TE)

PositionModuleTEFunction
1–2RCD 30 mA2Type A
3MCB B16A1Sockets kitchen
4MCB B20A1Oven (own circuit)
5MCB B16A1Dishwasher (own circuit)
6MCB B16A1Fridge (own circuit)
7MCB B16A1Sockets bedroom 1
8MCB B16A1Sockets bedrooms 2+3
9–18Spare10Blanking plates

Row 4 — Group 3: bathroom, outdoor, utility (18 TE)

PositionModuleTEFunction
1–2RCD 30 mA2Type A
3MCB B16A1Sockets bathroom
4MCB B16A1Washing machine (own circuit)
5MCB B16A1Tumble dryer (own circuit)
6MCB B20A1Water heater (own circuit)
7MCB B16A1Outdoor sockets
8MCB B16A1Garage
9–18Spare10Blanking plates

Total: 18 circuit breakers (compact 1P+N), 4 RCDs, SPD, main switch and bell transformer = 34 of 72 TE used, 53% spare. Each 30 mA RCD carries six final circuits and stays below the limit of eight. The hob and a future EV charger fit in the spare positions.

Common mistakes in board planning

MistakeConsequenceSolution
Too few rowsNo space, no thermal headroomSize from module count, wiring and enclosure data
Omitting the SPD without analysisProtection concept remains unprovenCheck applicability and selection for the project
More than 8 final circuits per 30 mA RCDBreach of 4.2.4.3 bAdd another RCD
Missing labelsBreach of 3.1.3.1Label every protective device (circuit identifier and function)
No RCD at the originProtection chain at the origin incompleteProvide a device of at most 300 mA, at least Type A and 40 A
Choosing EV charger protection by defaultDC fault protection may be insufficientCheck chapter 7.22, integrated DC detection and manufacturer data together
Ignoring the earth resistanceToo few RCDs above 30 ΩWait for the earth measurement or reserve space for extra devices
No usable spare capacityExtension becomes unnecessarily complexPlan module, terminal and wiring reserve per project

Labelling and documentation

Subsection 3.1.3.1 requires control, protective and isolating devices to be labelled clearly, conspicuously and indelibly. The board itself carries its own identifier and the supply voltage (3.1.3.3). Label each protective device with:

  • the circuit identifier, identical to the single-line diagram and situation plan (on the single-line diagram a capital letter identifies the circuit, 3.1.2.1),
  • the function, for example “Lighting ground floor” or “Sockets kitchen”,
  • optionally the room or floor.

Use a label strip or stick the overview inside the door; most manufacturers supply writable inserts.

From a layout sketch to an executable design

Counting modules is the spatial starting point. Before ordering, the electrician checks the connection data, earthing system, prospective short-circuit current, selectivity or back-up protection and the manufacturer approvals for combined devices. You therefore never copy rated current, breaking capacity or cross-section from an example without checking. Power dissipation in the closed enclosure, ambient temperature, ventilation and permitted terminal loading also shape the choice.

Work row by row. Record supply, main isolation, residual-current protection and surge protection as a traceable protection chain. Then arrange the final circuits, but do not mistake a visually tidy row for electrical selectivity. With PV, a battery, a generator or charging infrastructure, show clearly from which direction energy can flow and which parts may remain energised with the grid switched off. Manufacturer documents for the RCD, SPD, inverter or EV charger are binding design inputs.

Before export you align three levels: the physical occupancy of the board, the protection chain in the single-line diagram and the circuit identifiers on the situation plan show the same state. Book 1 V06 requires schemas, plans and documents to carry an unambiguous number, version and version date (section 3.1.2). For domestic installations, the name, capacity and VAT number (if applicable) of the person responsible and the installation address also appear on the single-line diagram and situation plan (3.1.2.1 a).

Board handover record

Before closing the cover, record for every outgoing circuit its identifier, purpose, number of poles, protective device, rated current, cable data and associated RCD. For controllable loads, add contactor, control circuit and manual operation. For multi-phase outgoing circuits, document the phases used; for single-phase circuits, a phase list helps you spot later imbalance. Check that each neutral is assigned to the correct RCD and that protective-conductor terminals stay accessible.

A photo complements the structured data but does not replace it. Terminal markings match the diagram and the label strip. Only record tightening torques or thermal follow-up checks when they come from manufacturer instructions or an execution record.

Also check mechanical accessibility: covers can still be fitted, conductors do not run in front of operating devices and measuring points remain reachable. Record separate N bars, links and supplies traceably. A spare position without a safe connection option is not usable spare capacity.

Keep the approved PDF together with the inspection report, measurement records and relevant data sheets in the installation file. When you extend later, do not overwrite the old file: increase the version, set a new version date and describe the change. That keeps it traceable which drawing showed the real board at which inspection.

Planning the board in PlanElec

In the PlanElec Board Editor you place modules on DIN rails, automatically or by hand; enclosure suggestions take recorded module widths, spare capacity and accessories into account. For existing installations, PlanElec recognises visible DIN modules in photos and turns them into a layout proposal you review. The AREI/RGIE self-check flags, among other things, an overfilled board, more than eight final circuits on a 30 mA RCD, a missing RCD at the origin, a main switch or main RCD below 40 A and socket circuits without 30 mA protection; less than 20% spare capacity appears as a tip. Measurements, manufacturer evidence and the inspection by the recognised inspection body remain separate steps. The rules covered are listed in what the self-check verifies.

Official basis

  • FPS Economy: RGIE/AREI, Book 1
  • Book 1 V06: sections 3.1.2 and 3.1.3 (schemas, plans, labelling), subsections 4.2.4.3, 4.4.1.4, 5.2.1.2, 5.3.5.1 to 5.3.5.3; sealing abolished by version 07 from 01.11.2026.

Plan your board in the PlanElec Board Editor and check it yourself →