Draw a Situation Plan: Step-by-Step Guide According to AREI/RGIE
Complete guide to creating an AREI/RGIE-compliant situation plan. From floor plan preparation to AREI symbols to the finished drawing.
Draw a Situation Plan: Step-by-Step Guide According to AREI/RGIE
The situation plan (also called position plan or plan de situation) shows where exactly each electrical component is located in your building. Together with the single-line diagram, it is one of the two mandatory documents for every electrical installation in Belgium — without it, the inspection by the approved control body will not pass.
In brief: While the single-line diagram shows the logical wiring (which switch controls which light, via which circuit), the situation plan shows the physical position of each component on the floor plan.
In this guide, you will learn how to create a standards-compliant situation plan step by step.
Step 1: Prepare the Floor Plan
Dimensions and Scale
The floor plan forms the basis of your situation plan. You can take it from a construction plan or draw it yourself.
Important:
- Use a uniform scale (common: 1:50 or 1:100).
- Draw all walls, doors, and windows.
- Mark the opening direction of doors (quarter circle) — this affects switch placement.
Label the Rooms
Give each room its designation and ideally its area:
| Abbreviation | Room | Typical Area |
|---|---|---|
| LR | Living Room | 25–40 m² |
| KI | Kitchen | 10–20 m² |
| BR | Bedroom | 12–18 m² |
| BA | Bathroom | 5–10 m² |
| HA | Hallway | 5–15 m² |
| GA | Garage | 15–30 m² |
| BS | Basement | variable |
| EX | Exterior | variable |
Step 2: Use AREI/RGIE Symbols
The AREI prescribes in Table 2.23 exactly which symbols must be used. These are based on the IEC 60617 standard. Here are the 10 most important symbols for the situation plan:
| No. | Symbol | Description | Usage |
|---|---|---|---|
| 1 | ⏚ Semicircle | Single socket outlet | Mark wall position |
| 2 | ⏚⏚ Double semicircle | Double socket outlet | Mark wall position |
| 3 | ○ with cross | Ceiling light | Centre of room/position |
| 4 | ─○ with line | Wall light | On the wall |
| 5 | Switch symbol | Single-pole switch | Next to door (opening side) |
| 6 | Switch symbol with 2 arrows | Series switch | Controls 2 luminaires |
| 7 | Switch symbol with line | Two-way switch | Two locations, one light |
| 8 | Rectangle with lightning | Distribution board | Usually hallway/utility room |
| 9 | ⏚ with PE | Earth connection | Earthing point |
| 10 | Circle with R | Smoke detector | Escape routes (hallway, staircase), regionally varies |
Tip: Use only the AREI/RGIE symbols. Self-invented symbols will be rejected during inspection.
Step 3: Draw the Components
Now place the symbols on the floor plan. The following rules help with correct positioning:
Socket Outlets
- Draw on the wall at the actual position.
- Kitchen: worktop at least 4 sockets, of which 2 above the counter. Dedicated sockets for oven, dishwasher, refrigerator.
- Living spaces: At least 1 socket per started 4 m² (practical recommendation by installer associations — the AREI does not prescribe a minimum number of sockets per area).
- Bathroom: Low-voltage sockets only from Zone 2 (bathtubs only, with 30mA RCD) or outside the zones. For showers, Zone 2 does not exist (Art. 7.1.3.2 Nr. 3b, Art. 7.1.5.2d).
- Outdoor: If an outdoor socket is installed, it must be weatherproof (IP44) and protected by a dedicated 30mA RCD.
Switches
- Next to the door on the opening side, approximately 105 cm height (practical recommendation — the AREI does not prescribe a specific switch height, but requires 'easily accessible').
- Two-way switches for rooms with multiple entrances or at the top/bottom of stairs.
- Connect switches and associated luminaires with a dashed line.
Lighting Points
- Ceiling lights in the centre of the room or at the planned position.
- Wall lights at the wall position.
- Every room needs at least one lighting point.
Smoke Detectors
Mandatory under Belgian fire safety legislation (varies by region):
- In Flanders: Mandatory in escape routes (hallways, staircases); recommended but not required in bedrooms.
- In Wallonia and Brussels, separate regulations apply.
- Hallways and staircases — at least one smoke detector per floor.
- In the kitchen optional (heat detector preferred to avoid false alarms).
Special Consumers
- EV charger (electric vehicle): garage or exterior wall, dedicated circuit.
- Water heater/Boiler: Dedicated circuit, mark the position.
- Heat pump/Air conditioning: Mark outdoor unit + indoor unit.
Step 4: Assign Circuit Numbers
Each component on the situation plan receives the same circuit number as in the single-line diagram. This is essential for identification during inspection.
How it works:
- Number your circuits in the single-line diagram (1, 2, 3, ...).
- Write the number next to each component on the situation plan.
- Use consistent notation: e.g., "C1" for circuit 1 or simply "1".
Example:
- Circuit 1: Ground floor lighting → All ground floor luminaires get "1".
- Circuit 2: Living room sockets → All living room sockets get "2".
- Circuit 3: Kitchen sockets → All kitchen sockets get "3".
- Circuit 4: Dedicated oven → One socket with "4".
Important: The numbers must match exactly between the single-line diagram and the situation plan. Inconsistencies are one of the most common reasons for remarks during inspection.
Documentation requirement: Art. 9.1.2 Nr. 1 (single-line diagram) and Art. 9.1.2 Nr. 2 (situation plan).
Step 5: Legend and Labelling
Complete your plan with:
- Legend with all symbols used and their meaning.
- Title block (cartouche) with: owner's name, address, date, plan creator, scale.
- North arrow (optional, but helpful).
- Floor indication for multi-storey buildings (one plan per floor).
Common Mistakes
| Mistake | Consequence | Solution |
|---|---|---|
| Missing smoke detectors | Inspection failed | Min. 1 per floor in escape routes (varies by region) |
| Outdoor socket not compliant | Remark, if present but non-compliant | If installed: IP44, dedicated 30mA RCD. A missing outdoor socket is not a fail reason |
| Missing labels / circuit numbers | Remark | Number every component |
| Wrong symbols | Remark | Use only AREI Table 2.23 |
| Switch on wrong side of door | Impractical (not an AREI violation) | Check opening direction |
| Bathroom socket in Zone 0 or 1 | Inspection failed | Sockets only from Zone 2 (bathtub) or outside the zones (shower) (Art. 7.1.5.2c/d) |
| No legend | Remark | Include symbol table |
Checklist Before Submission
- All rooms labelled
- All sockets, switches, lighting points drawn
- Smoke detectors in escape routes (min. 1 per floor, varies by region)
- Outdoor sockets, if installed, compliant (IP44, dedicated 30mA RCD)
- Circuit numbers on every component
- Numbers match the single-line diagram
- AREI symbols used (Table 2.23)
- Legend present
- Title block with name, address, date
- One plan per floor
Related Articles
- What Is a Single-Line Diagram?
- Electrical Inspection in Belgium
- Distribution Board Planning: Layout and Sizing
With PlanElec, create your situation plan directly from the floor plan — draw rooms, drag and drop devices, AREI symbols are used automatically. Try for free →