Free calculator for Belgium

Calculate voltage drop and cable cross-section

Check a selected cross-section or estimate a preliminary size, with no sign-up required.

Cable run data

Supply network

The network type sets the nominal voltage and the calculation. In a 3×230 V network the permitted voltage drop is smaller in volts than at 400 V.

m

Do not enter the return path; the formula already accounts for it.

Preliminary cross-section

2.5 mm²

Suitable in this preliminary check

Calculated current

16 A

3.5 kW

Voltage drop

2.78 %

Voltage at load

223.62 V

Minimum from protection and circuit type: 2.5 mm²

All cross-sections compared

Limit 5 %

suitable
meets both the limit and the breaker minimum
too thin for the breaker
voltage drop is fine, but too thin for the breaker
voltage drop too high
voltage drop above the limit

Checked are the voltage drop and the minimum from Table 4.11. Installation method, grouping and ambient temperature can require a larger cross-section.

Reach over cable length
5 % 1.52.540 50 100 m ΔU

2.5 mm² stays within the limit up to 54 m.

BoardLoad230 V 223.62 V 30 m · 2.5 mm² −6.38 V
L N PESingle-phase circuit between line and neutral — 230 V.
Compare cross-sections
Cross-sectionΔUVoltage at loadReachesProtection
1.5 mm²10.64 V · 4.63 % 219.36 V32 mtoo thin
2.5 mm²6.38 V · 2.78 % 223.62 V54 msuitable
4 mm²3.99 V · 1.73 % 226.01 V86 msuitable
6 mm²2.66 V · 1.16 % 227.34 V130 msuitable
10 mm²1.6 V · 0.69 % 228.4 V216 msuitable
16 mm²1 V · 0.43 % 229 V346 msuitable
25 mm²0.64 V · 0.28 % 229.36 V540 msuitable
35 mm²0.46 V · 0.2 % 229.54 V757 msuitable
50 mm²0.32 V · 0.14 % 229.68 V1,081 msuitable
Create an electrical plan

Source and limits

Preliminary check based on AREI/RGIE Book 1 (version effective since 1 April 2026) and documented rules of good practice. This is not a complete cable design.

Not checked: installation method, grouping, temperature, reactance, short-circuit withstand, disconnection conditions, terminals and manufacturer data.

What does this tool calculate?

The protective device and circuit type set an initial minimum. Length and load can require a larger cross-section because of voltage drop. The larger result becomes the preliminary size.

Frequently asked questions

Which network type do I have?

1×230 V is the usual single-phase domestic connection. 3N~400/230 V with neutral is today’s three-phase connection. 3×230 V without neutral appears in older Belgian installations; the permitted voltage drop is smaller in volts there because it refers to 230 V rather than 400 V.

When does the tool use 400 V?

Only for a three-phase circuit, because 400 V exists only between two line conductors. A single-phase final circuit always uses 230 V — against neutral on 1×230 V and 3N~400/230 V, between two line conductors on 3×230 V. The formula differs too: factor 2 single-phase for the return conductor, √3 three-phase.

Is the length one-way or there and back?

Enter the one-way distance from the distribution board to the load. The single-phase factor of 2 accounts for the return path.

Are 3% and 5% literal AREI limits?

No. AREI/RGIE 5.2.5 refers to the rules of good practice. PlanElec uses the documented 3% for lighting and 5% for other final circuits as preliminary thresholds.

Is the result AREI compliant?

The result checks only part of cable sizing and does not replace a complete design or inspection.

Preliminary cross-section

2.5 mm²

2.78 %Suitable in this preliminary check